To avoid dangerous sparks between a component and the tank during the loading operation, the tank must be earthed. The basic function of the DCMT 3 is to automatically earth the tank to the ground, preventing dangerous sparks between the rig and the tank and minimizing operator error. DCMT3 is programmable and changes to the set up values for electrical recognition can be made. The value of resistance and capacitance limits are programmable. The site specific electrical signatures are pre-set during the manufacture stage and if necessary these can be controlled externally. The application should be specified when ordering. Main applications of the DCMT 3 are; - Tank truck earthing
- Barrel earthing
- Wagon earthing
Specifications
- Material: Aluminum casting Al-Si7Mg0,3
- Weight: 15.2 kg
- Working temperature: -40° C / +60° C (ATEX certificate from manufacturer, PEROLO, only -30° C)
- EEx explosion proof and intrinsic safety electronic board. EExd (ia) ia II C T6
- Waterproof IP 67 (CEI 60529)
- Numerical model (intel 386 processor)
- High insulation voltage relay (10.000 V), self checking relay conditions
- Homologation by LCIE Certificate No. 00.E6088X in accordance with standard EN 50.014
Spares & Accessories
If you cannot find what you are looking for below click here to complete our spares inquiry form.
Distributors
| Country |
|
Related Products
-
Our complete Loading Skids are compact in design and can be installed in a short time. They can be used for all oil and refined oil products as well as for chemical, food and hygiene applications.
|